5.7 H: Terminal Functions
u
H2: Multi-Function Output
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC, and P2/PC Function Selection
n
The drive has three multi-function output terminals.
No.
H2-01
Terminal MA, MB and MC Function Selection (relay)
H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
Setting 1: Zero Speed
Terminal closes when the output frequency falls below the minimum output frequency set to E1-09 or b2-01.
Status
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Setting 2: Speed Agree 1 (f
Closes when the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency reference regardless
of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note:
Detection works in forward and reverse.
174
Parameter Name
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 5.51 During Run Time Chart
Output frequency
or
motor speed
OFF
Zero Speed
Figure 5.52 Zero-Speed Time Chart
/f
Agree 1)
ref
out
Setting Range
0 to 1AA
0 to 1AA
0 to 1AA
Description
ON
Description
E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)
ON
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
E: Fault
37: During Frequency Output
E: Fault