LED Display
LCD Display
LOP
Cause
The pump load, measured based on the P1-18
setting (output current, kilowatts, or power),
has dropped below the level set in P1-19,
Prime Loss Level, for the time set in P1-20,
Loss of Prime Time, and the output
frequency has risen above P1-21, Prime Loss
Frequency. This is effective only when
P1-22 Loss of Prime Selection is set to 0
(fault).
LED Display
LCD Display
LOH20
LWL
Cause
The Low Water Level switch is activated,
defective, or P1-30, Low Water Digital Input
Configuration, is programmed incorrectly.
LED Display
LCD Display
N5l
Net Master Loss
Cause
Network Recovery is set to Fault MSL
(P9-27 = 3) and no message has been
received from the master within the time set
in P9-26.
LED Display
LCD Display
NOT5P
Cause
When the feedback deviates from the
setpoint at a level greater than P1-15, for a
time set in P1-16. This is effective only when
P1-17 is set to 0 (fault).
LED Display
LCD Display
n5e
Cause
The node setup terminal closed during run.
A Run command was issued while the node
setup function was active.
LED Display
LCD Display
Oc
Cause
The motor has been damaged due to
overheating or the motor insulation is
damaged
One of the motor cables has shorted out or
there is a grounding problem
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Loss of Prime
LOP
The pump has lost its prime.
• Check for a dry well, air in the system, or no water in the system. Restart the pump using the preferred
priming method suggested by the pump manufacturer.
• Set the Loss of Prime fault characteristics in P1-18, P1-19, P1-20, and P1-21.
• Drive response to this condition is controlled by P1-21, Loss of Prime Selection.
• Auto-restart of this fault is controlled by L5-51, Loss of Prime Fault Retry Selection and P1-23, Loss of
Prime Maximum Restart Time after Fault
Low Water Level
The "Low Water Level" digital input is active (H1-0o = 8F).
Raise the water level and/or adjust the Low Water Level switch.
Net Master Lost
MSL
The MEMOBUS master has been lost
• Increase the P9-26 setting to account for network latency.
• Verify that there is a drive on the network with parameter P1-01 set to 3 and P9-27 to 0.
• Check network connections and verify H5-01 and P9-25 settings for all drives on the network.
Not Maintaining Setpoint
NMS
The setpoint cannot be maintained and P1-17 is set to 0.
• Check for a blocked impeller, over cycling, or broken pipe.
• Set the Not Maintaining Setpoint fault characteristics in P1-16 and P1-17.
• Drive response to this condition is controlled by P1-17, Not Maintaining Setpoint Selection.
• Auto-restart of this fault is controlled by L5-50, Setpoint Not Met Retry.
Node Setup Error
nSE
A terminal assigned to the node setup function closed during run.
Stop the drive when using the node setup function.
Overcurrent
oC
Drive sensors detected an output current greater than the specified overcurrent level.
• Check the insulation resistance.
• Replace the motor.
• Check the motor cables.
• Remove the short circuit and reapply power to the drive.
• Check the resistance between the motor cables and the ground terminal.
• Replace damaged cables.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution