b3-19: Number of Speed Search Restarts
n
Sets the number of times the drive should attempt to find the speed and restart the motor using Speed Estimation Speed Search.
This function has no influence when Current Detection Speed Search is used (b3-24 = 0).
No.
b3-19
b3-24: Speed Search Method Selection
n
Sets the Speed Search method used.
Note:
For explanations of the Speed Search methods,
Estimation Type Speed Search (b3-24 = 1) on page
No.
b3-24
Setting 0: Current Detection Speed Search
Setting 1: Speed Estimation Speed Search
b3-25: Speed Search Wait Time
n
Sets the wait time between Speed Search restarts.
No.
b3-25
b4: Delay Timers
u
The timer function is independent of the drive operation and can be used to delay the switching of a digital output triggered
by a digital input signal. An On-delay and Off-delay can be separately set. The delay timer can help to get rid of chattering
switch noise from sensors.
To enable the timer function, a multi-function input must be set to "Timer input" (H1-oo = 18) and a multi-function output
must be set to "Timer output" (H2-oo = 12). Only one timer can be used.
b4-01/b4-02: Timer Function On/Off-Delay Time
n
b4-01 sets the On-delay time for switching the timer output. b4-02 sets the Off-delay time for switching the timer output.
No.
b4-01
b4-02
Timer Function Operation
n
When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer
function input is open for longer than the value set in b4-02, the timer output function switches off. The following diagram
demonstrates the timer function operation.
Multi-function Contact
Input: Timer Function
Multi-function Contact
Output: Timer Function
b5: PID Control
u
The drive has a built in PID (Proportional + Integral + Derivative) controller that can be used for closed loop control of system
variables such as pressure, temperature etc. The difference between the target and the feedback value (deviation) is fed into
the PID controller. The PID controller adjusts the drive output frequency in order to minimize the deviation, providing an
accurate control of the system variables.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Name
Number of Speed Search Restarts
Refer to Current Detection Type Speed Search (b3-24 = 0) on page 125
124.
Parameter Name
Speed Search Method Selection
Name
Speed Search Wait Time
Name
Timer Function On-Delay Time
Timer Function Off-Delay Time
ON
ON
b4-01
b4-02
Figure 5.17 Timer Operation
Setting Range
0 to 10
Setting Range
0 or 1
Setting Range
0.0 to 30.0 s
Setting Range
0.0 to 300.0 s
0.0 to 300.0 s
ON
ON
b4-01
b4-02
5.2 b: Application
Default
3
Refer to Speed
and
Default
0
Default
0.5 s
Default
0.0 s
0.0 s
On (Closed)
Off (Open)
On (Closed)
Off (Open)