YASKAWA iQpump Micro CIMR-PW Series User Manual page 98

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

4.8 iQpump Presets and Functions
• Decrease the lag fixed speed delay (P9-07)
• Increase the staging frequency level (P9-09)
• Increase the staging delay time (P9-11)
• Increase the de-staging delay time (P9-15)
• Increase the stabilization time (P9-16)
• Increase both the Add Freq Level and Add Dly Time
Table 4.12 Related Parameters for Duplex System with Fine Tuning Application Example
Description
Run Source: 1 (Terminals)
Node Address
Highest Node Address
Pump Mode: 3 (Network)
Feedback Source: 0 (Analog)
Lag Fixed Speed
Setpoint
Start Level
High Feedback Quick De-Stage
Setpoint Modifier
Add Drive Frequency Level
Add Drive Delay
<1> All other multiplexing and alternation parameters are set to default settings.
Duplex System with Jockey Pump Example
A customer requires a pump system with the following requirements:
• One small pump (the Jockey pump) will run the system during off-peak times.
• Two larger pumps will run the system when the demand is higher.
• The Jockey pump should not run when the two larger pumps are running.
• Pump wear is still an issue, but it is expected that the small pump will run longer hours and will always run first after a loss
of power.
• The feedback scale is 145 PSI.
• There is only one feedback transducer in the system.
Table 4.13 Related Parameters for Duplex System with Jockey Pump Example
Description
Node Address
Highest Node Address
98
P9-06 = 54.0 Hz
U5-99 = 100 PSI
P1-04 = 140 PSI
P9-18 = 89.3%
P9-17 = 5.0 PSI
P9-09 = 59.0 Hz
S1
SN
(Jockey Pump)
10 HP
+V
A1
A2
AC
R+
R-
S+
S-
Figure 4.15 Simplified Wiring Diagram
<1>
Jockey Pump
H5-01 = 1
P9-25 = 3
<1>
Drive A
b1-02 = 1
H5-01 = 1
P9-25 = 2
P1-01 = 3
P9-02 = 0
P9-11 = 12.0 s
S1
SN
Drive B
15 HP
+V
A1
A2
AC
R+
R-
S+
S-
<1>
Drive B
H5-01 = 2
P9-25 = 3
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
<1>
Drive B
b1-02 = 1
H5-01 = 2
P9-25 = 2
P1-01 = 3
P9-02 = 0
P9-06 = 54.0 Hz
U5-99 = 100 PSI
P1-04 = 140 PSI
P9-18 = 89.3%
P9-17 = 5.0 PSI
P9-09 = 59.0 Hz
P9-11 = 12.0 s
S1
SN
Drive C
15 HP
+V
A1
A2
AC
R+
R-
S+
S-
Drive C
H5-01 = 3
P9-25 = 3
<1>