B.8 H Parameters: Multi-Function Terminals
No.
(Addr.
Name
Hex)
H3-04
Terminal A1 Bias
(0412)
Setting
H3-09
Terminal A2 Signal
(0417)
Level Selection
H3-10
Terminal A2 Function
(0418)
Selection
H3-11
Terminal A2 Gain
(0419)
Setting
H3-12
(041A) Terminal A2 Bias
Setting
H3-13
Analog Input Filter
(041B)
Time Constant
H3-14
Analog Input Terminal
(041C)
Enable Selection
H3-16
Terminal A1 Offset
(0440)
H3-17
Terminal A2 Offset
(0441)
H3-oo
Function
Setting
0
Frequency bias
1
Frequency gain
Auxiliary frequency
2
reference 1
4
Output voltage bias
Overtorque/
7
undertorque
detection level
B
PID feedback
C
PID setpoint
Motor Temperature
E
(PTC Input)
F
Through mode
Differential PID
16
feedback
1F
Through mode
HAND Frequency
20
Reference
41
Output Voltage Gain
342
LCD Display
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Terminal A1 Bias
0: 0 to 10 V
Term A2 Level
1: -10 to 10 V
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A2.
Term A2 FuncSel
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Terminal A2 Bias
Sets a primary delay filter time constant for terminals A1 and
A1/A2 Filter T
A2. Used for noise filtering.
Determines which analog input terminals will be enabled when
A1/A2 Sel
a digital input programmed for "Analog input enable"
1: A1 Available
(H1-oo = C) is activated.
2: A2 Available
1: Terminal A1 only
7: All Available
2: Terminal A2 only
7: All terminals enabled
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
Term A1 Offset
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
Term A2 Offset
H3 Multi-Function Analog Input Settings
LCD Display
Freq Ref Bias
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
Freq Ref Gain
of -100 to 0%.
10 V = E1-04 (maximum output frequency)
Aux Reference1
Voltage Bias
10 V = E1-05 (motor rated voltage)
10 V = Drive rated current (V/f)
Torque Det Level
PID Feedback1
10 V = 100%
PID Set Point
10 V = 100%
E Motor PTC
10 V = 100%
Select this setting when using the terminal in a pass-through mode. The terminal
Not Used
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
10 V = 100%
PID Feedback 2
Not Used
Set this value when using the terminal in the pass-through mode.
Hand Freq. Ref.
Full scale: Max. frequency (E1-04)
V/f out gain
10 V = 100%
Description
Use DIP Switch S1-2 to set input terminal A2 for
a current or voltage input signal.
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Values
Page
Default: 0.0%
183
Min.: -999.9
Max.: 999.9
Default: 2
184
Range: 0 to 3
Default: B
184
Range: 0 to 41
Default: 100.0%
Min.: -999.9
184
Max.: 999.9
Default: 0.0%
Min.: -999.9
184
Max.: 999.9
Default: 0.03 s
Min.: 0.00
184
Max.: 2.00
Default: 7
186
Range: 1, 2, 7
185
Min.: -500
Max.: 500
185
Min.: -500
Max.: 500