YASKAWA iQpump Micro CIMR-PW Series User Manual page 281

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

LED Display
LCD Display
Settings for N.C. and N.O. input for the
following functions were selected
simultaneously:
• External Search Command 1 and External
Search Command 2 (61 vs. 62)
• Fast Stop N.O. and Fast Stop N.C. (15 vs.
17)
• KEB Command 1 and KEB Command 2
(65, 66 vs. 7A, 7B)
• FWD Run Command (or REV) and FWD/
REV Run Command (2-wire) (40, 41 vs.
42, 43)
• External DB Command and Drive Enable
(60 vs. 6A)
One of the following settings was entered
while H1-oo = 2 (External Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse
train input selection is not set for the
frequency reference (H6-01 > 0)
• b1-15 or b1-16 set to 3 but no option card
is connected
• Although b1-15 = 1 (Analog Input) and
H3-02 or H3-10 are set to 0 (Frequency
Bias)
H2-oo is set to 38 (Drive Enabled) and H1-
oo is not set to 6A (Drive Enable).
LED Display
LCD Display
ope04
oPE04
Cause
The drive, control board, or terminal board
have been replaced and the parameter
settings between the control board and the
terminal board no longer match.
LED Display
LCD Display
ope05
oPE05
Cause
Frequency reference is assigned to an option
card (b1-01 = 3) and an input option card is
not connected to the drive.
The Run command is assigned to an option
card (b1-02 = 3) and an input option card is
not connected to the drive.
Frequency reference is assigned to the pulse
train input (b1-01 = 4) and terminal RP is not
set for frequency reference input (H6-01 > 0)
LED Display
LCD Display
ope07
oPE07
Cause
H3-02 and H3-10 are set to the same value.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
• Check if contradictory settings have simultaneously been assigned to the multi-function input terminals.
• Correct setting errors.
Correct the settings for the multi-function input terminal parameters.
Initialization Required, Term <–> Ctrl Chg
• Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the drive.
• Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220.
Run Command/Frequency Reference Source Selection Error
Reconnect the input option card to the drive.
Set H6-01 to 0.
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PID functions
conflict.
Change the settings to H3-02 or H3-10 so that functions no longer conflict.
Note:
Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02 or H3-10
simultaneously.
6.5 Operator Programming Errors
Error Name
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
6
281