YASKAWA iQpump Micro CIMR-PW Series User Manual page 103

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

T1-02: Motor Rated Power
n
Used to set the motor rated power according to the motor nameplate value. For optimal performance, the motor rated power
should be between 50 and 100% of the drive rating.
No.
T1-02
<1> The setting range differs based on drive software version.
PRG: 1016 and later: 0.03 to 650.00 kW
PRG: 1015 and earlier: 0.00 to 650.00 kW
T1-04: Motor Rated Current
n
Used to set the motor rated current according to the motor nameplate value. For optimal performance in OLV, the motor rated
current should be between 50 and 100% of the drive rating. Enter the current at the motor base speed.
No.
T1-04
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Name
Motor Rated Power
Name
Motor Rated Current
4.9 Auto-Tuning
Setting Range
<1>
Setting Range
10 to 200% of drive rated
current
Default
Determined by
o2-04 and C6-01
Default
Determined by
o2-04 and C6-01
4
103