YASKAWA iQpump Micro CIMR-PW Series User Manual page 365

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
P9-26
Master Time-out
(0E0D)
P9-27
Network Recovery
(0E0E)
P9-28
NETSCAN Alarm Time NETSCAN AlrmTime
(0E0F)
P9-29
(0E10)
Net Start Delay
P9-30
Lag Drive Speed
(0E11)
Follower Gain
P9-31
Lag Drive Speed
(0E12)
Follower Bias
P9-32
Lag Follower
(0E13)
Deceleration Time
P9-33
Lag Follower
(0E14)
Deceleration Time
Active Time
P9-34
Low Feedback Quick
(0E15)
De-Stage
P9-99
Network Compatibility
(0E56)
Selection
<1> Unit is determined by P1-02, System Units; scaling is determined by P1-03, Feedback Device Scaling; resolution is determined by b5-39, PID
System Units Display Digits.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
LCD Display
Sets the minimum amount of time that the slave drives will wait
Master Time-out
for a message from the master before performing the action set
in P9-27.
Determines the drive response when no messages are received
from the master for the time set in P9-26.
Network Recovery
0: Automatic. The drive will attempt to assume master
0: Automatic
functionality.
1: Slave/Resume
1: Slave/Resume. The drive will continue running when the
2: Slave/Stop
master is lost and will wait for a master to come online.
3: Fault MSL
2: Slave/Stop. The drive will stop running when the master is
lost and will wait for a master to come online.
3: Fault MSL. Fault the drive with an MSL (Master Lost).
Sets the amount of time that the slave drives will wait for a
message from the master before displaying a NETSCAN alarm.
Sets the amount of time that the network will wait before
selecting and starting the lead drive after the first drive on the
Net Start Delay
network has been put on AUTO Mode.
Sets the gain to be applied to the speed of the current lead drive
when P9-05 is set to 3. The bias to be applied is set in P9-31.
Lag Followr Gain
Sets the bias to be applied to the speed of the current lead drive
when P9-05 is set to 3. The gain to be applied is set in P9-30.
Lag Followr Bias
Sets the deceleration time when the P9-33 timer is running and
the drive is running as Lag Drive Speed Follower (P9-05 is set
Lag Followr Dcel
to 3).
Sets the time during which the deceleration time set in P9-32 is
effective. The drive will use the standard deceleration rate when
Lag Followr Dtim
it expires.
Setting this parameter to 0.0 disables the function.
Sets the low feedback level that will trigger a quick de-stage.
The quick de-stage ignores parameters P9-12 and P9-15 and
Low FB De-stage
only uses an internal 2 second delay.
Setting this parameter to 0.0 disables the function.
Determines the communication compatibility for the iQPump
Network Comp Sel
MEMOBUS network.
0: A-Ver: 30034
0: A-Ver: 30034
1: B-Ver: 30035/36
1: B-Ver: 30035/36
2: iQ SmartNetwork
2: iQ SmartNetwork
B.12 P: Pump Parameters
Description
Values
Page
Default: 4.0 s
Min.: 1.0
243
Max.: 10.0
Default: 0
243
Range: 0 to 3
Default: 2.0 s
243
Min.: 1.0
Max.: 10.0
Default: 2.0 s
Min.: 0.0
243
Max.: 60.0
Default: 100.0%
Min.: 0.0
243
Max.: 300.0
Default: 0.00 Hz
Min.: -60.0
243
Max.: 60.0
Default: 60.0 s
244
Min.: 0.0
Max.: 1000.0
Default: 0.0 s
244
Min.: 0.0
Max.: 3600.0
Default: 0.0 PSI
<1>
244
Min.: 0.0
Max.: 6000.0
Default: 2
244
Range: 0 to 2
B
365

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents