No.
(Addr.
Name
Hex)
Run Command
b1-16
Selection 2
(01C5)
Run Source 2
b1-17
Run Command at Power
(01C6)
Up
u
b2: DC Injection Braking and Short Circuit Braking
No.
(Addr.
Name
Hex)
b2-01
DC Injection Braking
(0189)
Start Frequency
b2-02
DC Injection Braking
(018A)
Current
b2-03
DC Injection Braking
(018B)
Time at Start
b2-04
DC Injection Braking
(018C)
Time at Stop
b3: Speed Search
u
No.
(Addr
Name
Hex.)
b3-01
Speed Search Selection
(0191)
at Start
b3-02
Speed Search
(0192)
Deactivation Current
b3-03
Speed Search
(0193)
Deceleration Time
b3-05
Speed Search Delay
(0195)
Time
b3-06
Output Current 1 during
(0196)
Speed Search
Current Control Gain
b3-08
during Speed Search
(0198)
(Speed Estimation
Type)
b3-10
Speed Search Detection
(019A)
Compensation Gain
b3-14
Bi-Directional Speed
(019E)
Search Selection
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
LCD Display
Enabled when a multi-function digital input set for "External
Run Source 2
Reference" (H1-oo = 2) closes.
0: Operator
0: Operator
1: Digital Inputs
1: Digital Inputs
2: Communication
2: Communication
3: Option PCB
3: Option PCB
0: Disregarded. A new Run command must be issued after
Run Cmd @ Pwr On
power up.
0: Cycle Ext Run
1: Allowed. Drive will run immediately after power up if a Run
1: Accept Ext Run
command is present.
LCD Display
Sets the frequency at which DC Injection Braking starts when
DCInj Start Freq
"Ramp to stop" (b1-03 = 0) is selected.
Sets the DC Injection Braking current as a percentage of the
DCInj Current
drive rated current.
Sets DC Injection Braking time at start. Disabled when set to
DCInj Time@Start
0.00 seconds.
Sets DC Injection Braking time at stop.
DCInj Time@Stop
LCD Display
SpdSrch at Start
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the current level at which the speed is assumed to be
SpdSrch DeactCur
detected and Speed Search is ended. Set as a percentage of the
drive rated current.
Sets output frequency reduction time during Speed Search.
SpdSrch Dec Time
When using an external contactor on the output side, b3-05
Search Delay
delays executing Speed Search after a momentary power loss to
allow time for the contactor to close.
Sets the current injected to the motor at the beginning of Speed
Estimation Speed Search. Set as a coefficient for the motor rated
Srch Im Lvl1
current.
Sets the proportional gain for the current controller during Speed
Search.
Srch ACR P Gain
Sets the gain which is applied to the speed detected by Speed
Estimation Speed Search before the motor is reaccelerated.
Srch Detect Comp
Increase this setting if ov occurs when performing Speed Search
after a relatively long period of baseblock.
Bidir Search Sel
0: Disabled (uses the direction of the frequency reference)
0: Disabled
1: Enabled (drive detects which way the motor is rotating)
1: Enabled
Description
Description
Description
B.3 b: Application
Values
Page
Default: 0
123
Range: 0 to 3
Default: 1
123
Range: 0, 1
Values
Page
Default: 0.5 Hz
123
Min.: 0.0
Max.: 10.0
Default: 50%
124
Min.: 0
Max.: 75
Default: 0.00 s
Min.: 0.00
124
Max.: 10.00
Default: 0.50 s
Min.: 0.00
124
Max.: 10.00
Values
Page
Default: 0
127
Range: 0, 1
Default: 120%
Min.: 0
127
Max.: 200
Default: 2.0 s
Min.: 0.1
127
Max.: 10.0
Default: 0.2 s
Min.: 0.0
127
Max.: 100.0
<1>
Default:
128
Min.: 0.0
Max.: 2.0
Default: 0.50
128
Min.: 0.00
Max.: 6.00
Default: 1.05
128
Min.: 1.00
Max.: 1.20
Default: 0
128
Range: 0, 1
B
321