YASKAWA iQpump Micro CIMR-PW Series User Manual page 284

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

6.6 Copy Function Related Displays
LED Display
LCD Display
ndat
Cause
The drive from which the parameters were
copied and the drive to which the parameters
will be written have different electrical
specifications, capacities, are set to different
control modes, or are different models.
The device being used to write the
parameters is blank and does not have any
parameters saved on it.
LED Display
LCD Display
rder
Cause
Failed while attempting to read parameter
settings from the drive.
LED Display
LCD Display
read
Cause
Displayed while the parameter settings are
being read onto the USB Copy Unit.
LED Display
LCD Display
uAEr
Cause
The drive from which the parameters were
copied and the drive on which the Verify
mode is being performed have different
electrical specifications or are a different
capacity.
LED Display
LCD Display
ufyE
Cause
Indicates that parameter settings that have
been Read and loaded onto the Copy Unit or
HOA keypad are different.
LED Display
LCD Display
urfy
Cause
The Verify mode has confirmed that
parameters settings on the drive and
parameters read to the copy device are
identical.
284
Model, Voltage Class, Capacity Mismatch
ndAT
Make sure model numbers and specifications are the same for both drives.
Make sure all connections are correct, and copy the parameter settings onto the USB Copy Unit or the HOA
keypad.
Error Reading Data
rdEr
Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read parameters
from the drive.
Reading Parameter Settings (flashing)
rEAd
This is not an error.
Voltage Class, Capacity Mismatch
vAEr
Make sure electrical specifications and capacities are the same for both drives.
Parameter settings in the drive and those saved to the copy function are not the same
vFyE
To synchronize parameters, either write the parameters saved on the USB Copy Unit or HOA keypad onto
the drive, or Read the parameter settings on the drive onto the USB Copy Unit.
Comparing Parameter Settings (flashing)
vrFy
This is not an error.
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents