YASKAWA iQpump Micro CIMR-PW Series User Manual page 214

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

5.9 n: Special Adjustments
n3-21: High Slip Suppression Current Level
n
If overcurrent, oL1, or oL2 occur during overexcitation deceleration, reduce the overslip suppression current level. Set as a
percentage of the drive rated current.
Reduce this setting if the current during overexcitation deceleration exceeds the overslip suppression current set in n3-21 as
a result of flux saturation and excessive slip. Alternatively reduce the overexcitation gain n3-13.
No.
n3-21
n3-23: Overexcitation Operation Selection
n
Determines which direction overexcitation can be used in. However, parameter L3-04 must be set to 4 in order for n3-23 to
be enabled.
No.
n3-23
Setting 0: Enabled in Both Directions
Setting 1: Enabled in Forward Direction Only
Setting 2: Enabled in Reverse Direction Only
214
Name
Overslip Suppression Current Level
Name
Overexcitation Operation Selection
Setting Range
0 to 150%
Setting Range
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
100%
Default
0 to 2
0