H4: Analog Outputs
u
No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal AM
(041D)
Monitor Selection
H4-02
Multi-Function Analog
(041E)
Output Terminal AM
Gain
H4-03
Multi-Function Analog
(041F)
Output Terminal AM
Bias
u
H5: MEMOBUS/Modbus Serial Communication
No.
(Addr.
Name
Hex)
H5-01
(0425)
Drive Node Address
<1>
H5-02
Communication Speed
(0426)
Selection
H5-03
Communication Parity
(0427)
Selection
Stopping Method after
H5-04
Communication Error
(0428)
(CE)
H5-05
Communication Fault
(0429)
Detection Selection
H5-06
Drive Transmit Wait
(042A)
Time
H5-07
RTS Control Selection
(042B)
H5-09
CE Detection Time
(0435)
Unit Selection for
H5-10
MEMOBUS/Modbus
(0436)
Register 0025H
Communications
H5-11
ENTER Function
(043C)
Selection
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
LCD Display
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
Term AM FuncSel
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal AM that is equal to 100% of the
selected monitor value.
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Terminal AM Bias
LCD Display
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
Serial Comm Adr
to take effect.
Serial Baud Rate
0: 1200 bps
0: 1200 bps
1: 2400 bps
1: 2400 bps
2: 4800 bps
2: 4800 bps
3: 9600 bps
3: 9600 bps
4: 19200 bps
4: 19.2 kbps
5: 38400 bps
5: 38.4 kbps
6: 57600 bps
6: 57.6 kbps
7: 76800 bps
7: 76.8 kbps
8: 115200 bps
8: 115.2 kbps
Cycle power for the setting to take effect.
Serial Com Sel
0: No parity
0: No parity
1: Even parity
1: Even parity
2: Odd parity
2: Odd parity
Cycle power for the setting to take effect.
Serial Fault Sel
0: Ramp to stop
0: Ramp to Stop
1: Coast to stop
1: Coast to Stop
2: Fast Stop
2: Fast-Stop
3: Alarm only
3: Alarm Only
Serial Flt Dtct
0: Disabled
0: Disabled
1: Enabled. If communication is lost for more than two seconds,
1: Enabled
a CE fault will occur.
Set the wait time between receiving and sending data.
Transmit WaitTIM
RTS Control Sel
0: Disabled. RTS is always on.
0: Disabled
1: Enabled. RTS turns on only when sending.
1: Enabled
Sets the time required to detect a communications error.
CE Detect Time
Adjustment may be needed when networking several drives.
CommReg 25h Unit
0: 0.1 V units
0: 0.1 V
1: 1 V units
1: 1 V
0: Drive requires an Enter command before accepting any
Enter CommandSel
changes to parameter settings.
0: Enter Required
1: Parameter changes are activated immediately without the
1: No EnterRequired
Enter command.
B.8 H Parameters: Multi-Function Terminals
Description
Description
Values
Page
Default: 102
186
Range: 000 to
999
Default: 100.0%
Min.: -999.9
186
Max.: 999.9
Default: 0.0%
Min.: -999.9
186
Max.: 999.9
Values
Page
Default: 1F
(Hex)
391
Min.: 0
<2>
Max.: FF
Default: 3
391
Range: 0 to 8
Default: 0
391
Range: 0 to 2
Default: 3
392
Range: 0 to 3
Default: 1
392
Range: 0, 1
Default: 5 ms
Min.: 5
392
Max.: 65
Default: 1
392
Range: 0, 1
Default: 2.0 s
Min.: 0.0
392
Max.: 10.0
Default: 0
393
Range: 0, 1
Default: 0
394
Range: 0, 1
B
343