5.7 H: Terminal Functions
Setting 13: Speed Agree 2 (f
The output closes when the actual output frequency is within the speed agree width (L4-04) of the current frequency reference,
regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-04.
Note:
Detection works in forward and reverse.
Output Frequency
Speed Agree 2
Setting 14: User-Set Speed Agree 2 (f
The output closes when the actual output frequency and the frequency reference are within the speed agree width (L4-04) of
the programmed speed agree level (L4-03).
Status
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency reference
Output frequency
User Set
Speed Agree 2
Setting 15: Frequency Detection 3
The output opens when the output frequency rises above the detection level set in L4-03 plus the detection with set in L4-04.
The terminal remains open until the output frequency or motor speed falls below the level set in L4-03. The detection level
L4-03 is a signed value; detection works in the specified direction only.
Status
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
178
/f
Agree 2)
ref
out
Frequency
reference
or Motor Speed
OFF
ON
Figure 5.57 Speed Agree 2 Time Chart
/f
Agree 2)
ref
set
L4-03
0 Hz
OFF
ON
Figure 5.58 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Description
L4-04
Description
Frequency reference
L4-03
+
Frequency reference – L4-04
L4-03 – L4-04
During
Forward
OFF
ON
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
L4-04
+
L4-04
L4-04
Output frequency
Frequency
reference