Connection is broken or master controller
stopped communicating.
Option is damaged.
The option is not properly connected to the
drive.
A data error occurred due to noise.
LED Display
LCD Display
cAll
CALL
Cause
Communications wiring is faulty, there is a
short circuit, or something is not connected
properly.
Programming error on the master side.
Communications circuitry is damaged.
Termination resistor setting is incorrect.
LED Display
LCD Display
ce
Cause
A data error occurred due to noise.
Communication protocol is incompatible.
The CE detection time (H5-09) is set shorter
than the time required for a communication
cycle to take place.
Incompatible PLC software settings or there
is a hardware problem.
Communications cable is disconnected or
damaged.
LED Display
LCD Display
no indication
Clock Not Set
Cause
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
If there are no problems with the wiring and the fault continues to occur, replace the option.
• The connector pins on the option are not properly lined up with the connector pins on the drive.
• Reinstall the option.
• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring.
• Try to reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
• Use recommended cables or some other type of shielded line. Ground the shield to the controller side
or on the input power side.
• Separate the wiring for communication devices from the drive input power lines. Install an EMC noise
filter to the drive input power.
Serial Communication Transmission Error
Communication has not yet been established.
• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
Check communications at start-up and correct programming errors.
• Perform a self-diagnostics check.
• If the problem continues, replace the drive.
Install a termination resistor at both ends of a communication line. Set the internal termination resistor
switch correctly on slave drives. Place DIP switch S2 to the ON position.
MEMOBUS/Modbus Communication Error
CE
Control data was not received correctly for two seconds.
• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground wiring.
• Reduce noise on the controller side.
• Use surge absorbers for the magnetic contactors or other components that may be causing the
disturbance.
• Use only recommended shielded line. Ground the shield on the controller side or on the drive input
power side.
• Separate all wiring for communication devices from drive input power lines. Install an EMC noise filter
to the drive input power supply.
• Check the H5 parameter settings and the protocol setting in the controller.
• Ensure settings are compatible.
• Check the PLC.
• Change the software settings in the PLC.
• Set a longer CE detection time using parameter H5-09.
• Check the PLC.
• Remove the cause of the error on the controller side.
• Check the connector to make sure the cable has a signal.
• Replace the communications cable.
Clock Not Set
Possible Solution
Minor Fault Name
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
6.4 Alarm Detection
269