5.11 P: Pump
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high
feedback detection are no longer true, the digital output will open.
P1-14: Hysteresis Level
n
Sets the hysteresis level used for low and high feedback detection.
No.
P1-14
P1-15: Maximum Setpoint Difference
n
When the system is running and the difference between the setpoint and feedback exceeds the level set in P1-15 for the time
set in P1-16, the drive will respond according to the method selected in P1-17. On fault, the drive will coast to stop.
Setting this parameter to 0.0 disables the function. This function is active only when running while in AUTO Mode. When
P1-01 is set to 3, the function is active on the lead drive and will stop all drives running on the network when the NMS fault
occurs (system fault).
No.
P1-15
P1-16: Not Maintaining Setpoint Time
n
Sets the delay time before a "Setpoint Not Met" condition occurs. Pump protection criteria specified in P1-15 must be met
before the timer will start. Setting P1-15 to 0 disables NMS detection.
No.
P1-16
P1-17: Not Maintaining Setpoint Selection
n
No.
P1-17
Setting 0: Fault
The "NMS – Setpoint Not Met" alarm is shown on the HOA keypad and the digital output closes when the PID feedback rises
above or falls below the setpoint for more than the P1-15 amount.
When the feedback returns to a value within the P1-15 setting before the Not Maintaining Set Point Time (P1-16) expires, the
alarm clears, the digital output opens, and the timer resets. If the NMS condition persists for longer than the time set in P1-16,
the drive will fault out on a "NMS – Setpoint Not Met" fault and coast to a stop. The digital output remains closed until the
fault is reset.
Setting 1: Alarm
The "NMS – Setpoint Not Met" alarm is shown on the HOA keypad and the digital output closes when the PID feedback rises
above or falls below the setpoint more than the P1-15 amount.
When the feedback returns to a value within the P1-15 level, the alarm clears and the digital output opens.
Setting 2: Digital out only
A digital output programmed to 93 closes. When the feedback returns to a value within the P1-15 level, the digital output
opens.
P1-18: Prime Loss Detection Method
n
No.
P1-18
Loss of Prime (LOP) is enabled when one of the following conditions are true:
• P1-19 > 0 in AUTO Mode and Sleep Boost
• P4-05 > 0 in Pre-Charge 1 Mode
• P4-08 > 0 in Pre-Charge 2 Mode
• P5-06 > 0 in HAND Mode
• P5-07 > 0 in HAND Mode 2
226
Name
Hysteresis Level
Name
Maximum Setpoint Difference
Name
Not Maintaining Setpoint Time
Name
Not Maintaining Setpoint Selection
Name
Prime Loss Detection Method
Setting Range
0.0 to 100.0
Setting Range
0.0 to 6000.0
Setting Range
0 to 3600 s
Setting Range
Setting Range
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
0.0 PSI
Default
0.0 PSI
Default
60 s
Default
0 to 2
Default
0 to 2
0
0