B.5 d: References
No.
(Addr.
Name
Hex)
d1-14
(028F)
Frequency Reference 14 Reference 14
d1-15
(0290)
Frequency Reference 15 Reference 15
d1-16
(0291)
Frequency Reference 16 Reference 16
d1-17
Jog Frequency
(0292)
Reference
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
d2: Frequency Upper/Lower Limits
u
No.
(Addr.
Name
Hex.)
d2-01
Frequency Reference
(0289)
Upper Limit
d2-02
Frequency Reference
(028A)
Lower Limit
d2-03
Master Speed Reference
(0293)
Lower Limit
d3: Jump Frequency
u
No.
(Addr.
Name
Hex)
d3-01
Jump Frequency 1
(0294)
d3-02
Jump Frequency 2
(0295)
d3-03
Jump Frequency 3
(0296)
d3-04
Jump Frequency Width Jump Bandwidth
(0297)
328
LCD Display
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3, 4" (H1-oo = 3, 5, 32) are on.
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 3, 4" (H1-oo = 4, 5, 32) are on.
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2, 3, 4" (H1-oo = 3, 4, 5, 32) are on.
Frequency reference when digital inputs "Jog Frequency
Reference", "Forward Jog", or "Reverse Jog." are on. "Jog
Jog Reference
Frequency Reference" has priority over "Multi-Step Speed
Reference 1 to 16".
LCD Display
Sets the frequency reference upper limit as a percentage of the
Ref Upper Limit
maximum output frequency.
Sets the frequency reference lower limit as a percentage of the
Ref Lower Limit
maximum output frequency.
Sets the lower limit for frequency references from analog inputs
Ref1 Lower Limit
as a percentage of the maximum output frequency.
LCD Display
Eliminates problems with resonant vibration of the motor/
Jump Freq 1
machine by avoiding continuous operation in predefined
frequency ranges. The drive accelerates and decelerates the
motor through the prohibited frequency ranges.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Jump Freq 2
Setting this parameter to 0.0 disables the function.
Jump Freq 3
Sets the dead-band width around each selected prohibited
frequency reference point.
Description
Description
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Values
Page
Default: 0.00 Hz
Min.: 0.00
147
Max.: 400.00
<1>
Default: 0.00 Hz
Min.: 0.00
147
Max.: 400.00
<1>
Default: 0.00 Hz
Min.: 0.00
147
Max.: 400.00
<1>
Default: 6.00 Hz
Min.: 0.00
147
Max.: 400.00
<1>
Setting
Page
Default: 100.0%
Min.: 0.0
148
Max.: 110.0
Default: 0.0%
Min.: 0.0
148
Max.: 110.0
Default: 0.0%
Min.: 0.0
149
Max.: 110.0
Values
Page
Default: 0.0 Hz
Min.: 0.0
149
Max.: 400.0
Default: 0.0 Hz
Min.: 0.0
149
Max.: 400.0
Default: 0.0 Hz
Min.: 0.0
149
Max.: 400.0
Default: 1.0 Hz
149
Min.: 0.0
Max.: 20.0