YASKAWA iQpump Micro CIMR-PW Series User Manual page 179

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

Frequency
detection 3
Setting 16: Frequency Detection 4
The output closes when the output frequency is above the detection level set in L4-03. The terminal remains closed until the
output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Status
Open
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Closed
Output frequency or motor speed exceeded L4-03.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency
Detection 4
Setting 1A: During Reverse
A digital output set for "During reverse" closes when the drive is running the motor in the reverse direction.
Status
Open
Motor is being driven in the forward direction or stopped.
Closed
Motor is being driven in reverse.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Output Frequency
or Motor Speed
OFF
ON
Figure 5.59 Frequency Detection 3 Example with a Positive L3-04 Value
Output Frequency
or Motor Speed
OFF
ON
Figure 5.60 Frequency Detection 4 Example with Positive L3-04 Value
Output frequency
FWD Run command
REV Run command
During Reverse
Figure 5.61 Reverse Direction Output Example Time Chart
L4-04
L4-03
Description
L4-04
L4-03
Description
OFF
ON
5.7 H: Terminal Functions
time