Setting 9: Frequency Reference Source
Displays the currently selected frequency reference source.
Status
Open
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).
Closed
Frequency reference is being sourced from the digital operator.
Setting A: Run Command Source
Displays the currently selected Run command source.
Status
Open
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Closed
Run command is being sourced from the digital operator.
Settings B, 17, 18, and 19: Torque Detection 1 (N.O., N.C.), Torque Detection 2 (N.O., N.C.)
These digital output functions signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below.
Setting
Status
B
Closed
17
Open
18
Closed
19
Open
Setting C: Frequency Reference Loss
An output set for this function closes when frequency reference loss is detected.
Setting D: Braking Resistor Fault
An output programmed for this function closes when the dynamic braking resistor (DB) overheats or the braking transistor is
in a fault condition.
Setting E: Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting F: Through Mode
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function in
the drive. Setting F, however, still allows the status of the output terminal (open or closed) to be read by a PLC via a
communication option or MEMOBUS/Modbus communications.
Setting 10: Minor Fault (Alarm)
The output closes when a minor fault (alarm) condition is present.
Setting 11: Fault Reset Command Active
The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,
or using a communications option card.
Setting 12: Timer Output
This setting configures a digital output terminal as the output for the timer function.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Torque detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 2 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
Torque detection 2 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
Description
Description
Description
Description
5.7 H: Terminal Functions