5.5 E: Motor Parameters
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the Test Report at 115 °C.
E2-06: Motor Leakage Inductance
n
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
No.
E2-06
E2-10: Motor Iron Loss for Torque Compensation
n
This parameter sets the motor iron loss in watts.
No.
E2-10
E2-11: Motor Rated Power
n
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto-
Tuning completes successfully, the value entered will automatically be saved to E2-11.
No.
E2-11
160
Parameter Name
Motor Leakage Inductance
Parameter Name
Motor Iron Loss for Torque Compensation
Parameter Name
Motor Rated Power
Setting Range
0.0 to 40.0%
Setting Range
0 to 65535 W
Setting Range
0.00 to 650.00 kW
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
Depending on
o2-04
Default
Depending on
o2-04
Default
Depending on
o2-04