H1-oo
Function
Setting
90
High Water Level
95
Remove Drive Disable Remote Drv Disbl
Emergency Override
AF
Forward Run
Emergency Override
B0
Reverse Run
u
H2: Multi-Function Digital Outputs
No.
(Addr.
Name
Hex)
Terminal MA, MB, and
H2-01
MC function selection
(040B)
(relay)
Terminal P1 function
H2-02
selection (open-
(040C)
collector)
Terminal P2 function
H2-03
selection (open-
(040D)
collector)
H2-06
Watt Hour Output Unit
(0437)
Selection
H2-oo
Function
Setting
0
During run
1
Zero speed
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
DC bus undervoltage
During baseblock
8
(N.O.)
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
LCD Display
Function active when the drive is running. Function logic depends on P1-31, High
Water Digital Input Configuration.
P1-31 = 0 (Normally open)
Closed: High water level fault
High Water
Open: Reservoir/Tank is filled to normal level
P1-31 = 1 (Normally closed)
Closed: Reservoir/Tank is filled to normal level
Open: High water level fault
Closed: Prevents the drive from running when active for the time set in P4-26.
Must be inactive for the time set in P4-27 to allow the drive to run again.
Note:
Closed: Run the drive forward using the speed set in S6-02.
EmergOverrideFWD
Closed: Run the drive in reverse using the speed set in S6-02.
EmergOverrideREV
LCD Display
Refer to H2 Multi-Function Digital Output Settings on pages
339
341
MA/MB/MC FuncSel
to
P1/PC Func Sel
P2/PC Func Sel
Outputs a 200 ms pulse signal when the watt-hour counter
increases by the units selected.
0: 0.1 kWh units
Pwr Mon Unit Sel
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Table B.3 H2 Multi-Function Digital Output Settings
LCD Display
During RUN 1
Closed: A Run command is active or voltage is output.
Open: Output frequency is above the minimum output frequency set in E1-09.
Zero Speed
Closed: Output frequency is below the minimum output frequency set in E1-09.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
Fref/Fout Agree1
set to L4-02).
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
Fref/Set Agree 1
hysteresis set to L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
Freq Detect 1
determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01 with
Freq Detect 2
hysteresis determined by L4-02.
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
BaseBlk 1
B.8 H Parameters: Multi-Function Terminals
Description
1. Parameter P4-25 determines if this input is normally open or
normally closed.
2. When P1-01 = 3, an alarm condition will cause this drive to be
unavailable to the network.
Description
for descriptions of setting values.
Description
Page
173
173
173
173
Values
Page
Default: E
174
Range: 0 to 1AA
Default: 37
174
Range: 0 to 1AA
Default: E
174
Range: 0 to 1AA
Default: 0
182
Range: 0 to 4
Page
174
174
174
175
175
176
176
176
176
B