Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.
H3-02: Terminal A1 Function Selection
n
Selects the input signal level for analog input A1.
No.
H3-02
H3-03, H3-04: Terminal A1 Gain and Bias Settings
n
Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1 (bias).
Use both parameters to adjust the characteristics of the analog input signal to terminal A1.
No.
H3-03
H3-04
Setting Examples
• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since
the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04
above 5 Vdc.
Figure 5.63 Frequency Reference Setting by Analog Input with Increased Gain
• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
Figure 5.64 Frequency Reference Setting by Analog Input with Negative Bias
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Name
Terminal A1 Function Selection
Name
Terminal A1 Gain Setting
Terminal A1 Bias Setting
H3-01 = 0
Gain = 200 %
Frequency
reference
100 %
E1-04
Bias = 0 %
0 V
5 V
H3-01 = 0
100 %
Frequency
H3-01 = 0
reference
0
2.0 V
10 V
Analog Input
-25%
Voltage
H3-01 = 1
H3-01 = 1
Gain = 200 %
100%
E1-04
-10 V
-5 V
0 V
-100%
E1-04
10 V
H3-01 = 1
100%
-10 V
-6.0 V
2.0 V
-25%
-100%
E1-04
-150%
5.7 H: Terminal Functions
Setting Range
0 to 41
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
5 V
10 V
Gain = -200 %
10 V
Analog Input
Voltage
Default
0
Default
100.0%
0.0%
5
183