5.4 d: Reference Settings
Multi-step Speed Ref. 1
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Multi-step Speed Ref. 4
Jog Reference
d2: Frequency Upper/Lower Limits
u
By entering upper or lower frequency limits, the drive programmer can prevent operation of the drive above or below levels
that may cause resonance and or equipment damage.
d2-01: Frequency Reference Upper Limit
n
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No.
d2-01
d2-02: Frequency Reference Lower Limit
n
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is input, the drive will run at the d2-02 level. If the drive is started with a lower reference
than d2-02, it will accelerate up to d2-02.
No.
d2-02
148
Frequency
reference
d1-04
d1-03
d1-02
(A2)
d1-01
(A1)
FWD (REV) Run/Stop
ON
ON
Figure 5.30 Preset Reference Timing Diagram
Parameter Name
Frequency Reference Upper Limit
Parameter Name
Frequency Reference Lower Limit
Internal frequency
reference
d2-01
Operating
range
d2-02
Figure 5.31 Frequency Reference: Upper and Lower Limits
d1-13
d1-12
d1-07
d1-06
d1-05
ON
ON
ON
ON
ON
ON
ON
Frequency Reference Upper Limit
Frequency Reference Lower Limit
Set frequency reference
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
d1-16
d1-15
d1-14
d1-17
Time
ON
ON
ON
ON
ON
ON
Setting Range
0.0 to 110.0%
Setting Range
0.0 to 110.0%
Default
100.0%
Default
0.0%