5.7 H: Terminal Functions
H6-04: Pulse Train Input Terminal RP Bias
n
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
No.
H6-04
H6-05: Pulse Train Input Terminal RP Filter Time
n
Sets the pulse train input filter time constant in seconds.
The pulse train input filter helps prevent noise interference from causing erroneous operation when operating the drive within
the pulse train signal.
Increasing the filter setting time increases the effectiveness of the noise prevention, however, this also increasingly slows drive
response time.
No.
H6-05
H6-06: Pulse Train Output Terminal MP Monitor Selection
n
Selects the pulse train monitor output terminal MP function. The set value ooo is equal to the numerals in Uo-oo of the
Refer to U: Monitors on page 369
selected monitor.
No.
H6-06
Pulse Train Output Terminal MP Monitor Selection
H6-07: Pulse Train Output Terminal MP Monitor Scaling
n
Pulse train monitor scaling sets the output frequency at terminal MP when the monitor item is 100%. Set H6-06 to 102 and
H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
No.
H6-07
H6-08: Pulse Train Input Minimum Frequency
n
Sets the minimum output frequency detected by the pulse train input. Increasing this setting reduces the time the drive needs
to react to changes in the input signal.
• The pulse input value becomes 0 when the pulse input frequency falls below this level.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No.
H6-08
188
Name
Pulse Train Input Bias
Name
Pulse Train Input Filter Time
for a complete list of monitors. Selectable monitor items are listed below.
Name
Name
Pulse Train Input Monitor Scaling
Name
Pulse Train Input Minimum Frequency
Setting Range
-100.0 to 100.0%
Setting Range
0.00 to 2.00 s
Setting Range
000, 031, 101, 102, 105, 116,
501, 502, 801 to 809
Setting Range
0 to 32000 Hz
Setting Range
0.1 to 1000.0 Hz
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
0.0%
Default
0.10 s
Default
102
Default
1440 Hz
Default
0.5 Hz