YASKAWA iQpump Micro CIMR-PW Series User Manual page 370

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

B.16 U: Monitors
No.
(Addr.
Name
Hex)
U1-11
Output Terminal
(004A)
Status
U1-12
Drive Status
(004B)
U1-13
Terminal A1 Input
(004E)
Level
U1-14
Terminal A2 Input
(004F)
Level
U1-16
Output Frequency after
(0053)
Soft Starter
U1-18
oPE Fault Parameter
(0061)
370
LCD Display
Displays the output terminal status.
U1 - 11=
Output Term Sts
Verifies the drive operation status.
U1 - 12=
Int Ctl Sts 1
Displays the signal level to analog input terminal A1.
Term A1 Level
Displays the signal level to analog input terminal A2.
Term A2 Level
Displays output frequency with ramp time and S-curves. Units
SFS Output
determined by o1-03.
Displays the parameter number that caused the oPE02 operation
OPE Error Code
error.
Description
00000000
1
Multi-Function
Digital Output (fault)
(terminal MA/MB-MC)
1
Multi-Function
Digital Output 1
(terminal P1) enabled
1
Multi-Function
Digital Output 2
(terminal P2) enabled
Multi-Function
Digital Output (fault)
(terminal MA/MB-MC)
Multi-Function
Digital Output 1
(terminal P1) enabled
Multi-Function
Digital Output 2
(terminal P2) enabled
00000000
1
During run
1
During zero-speed
1
During REV
1
During fault reset
signal input
1
During speed agree
1
Drive ready
1
During alarm
detection
1
During fault detection
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Analog
Unit
Output Level
No signal output
available
No signal output
available
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: Max
0.01 Hz
frequency
No signal output
available

Hide quick links:

Advertisement

Table of Contents
loading