YASKAWA iQpump Micro CIMR-PW Series User Manual page 341

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

H2-oo
Function
Setting
Braking transistor fault
4E
(rr)
Braking resistor
4F
overheat (oH)
58
Underload detection
89
Output I Limit
Lube Pump or Digital
8B
Output Delay
8F
Internal Fan On
91
Pump Fault
92
Transducer Loss
93
Setptoint Not Met
94
Loss of Prime
95
Volute Thermostat Fault Volute-TStat Flt
96
High Feedback
97
Low Feedback
A2
Sleep Active
A3
Start Delay
A4
Pre-Charge
A5
Anti-Jam Active
A9
Thrust Mode
AA
Utility Start Delay
100 to
Function 0 to AA with
1AA
inverse output
u
H3: Multi-Function Analog Inputs
No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal
(0410)
Level Selection
H3-02
Terminal A1 Function
(0434)
Selection
H3-03
Terminal A1 Gain
(0411)
Setting
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
LCD Display
Closed: The built-in dynamic braking transistor failed.
Brk Trans Fault
Closed: The dynamic braking resistor has overheated.
BrkResistOvHeat
UL6
Closed: Underload is detected.
Closed: Drive output speed is being limited due to the output current limit or the
Output I Lim
single phase foldback regulator.
Lube Pump or
Closed: Refer to Lube Pump / Digital Output Delay parameters P4-30 and P4-31.
DigitalOutput Delay
Display text is set by parameter P4-29.
Internal Fan On
Internal Fan On
Closed when any of the following faults are active:
• Low feedback
• High feedback
• Low water
Pump Fault
• High water
• NMS-Setpoint not met
• POC-Pump over cycle
• THMS-Thermostat input
• External pump fault
Closed: The analog output associated with PID feedback has risen above 21 mA
Transducer Loss
or fallen below 3 mA or a Transducer Loss alarm or fault is active.
SetPoint Not Met
Closed: During an "NMS-Setpoint Not Met" condition.
Loss of Prime
Closed: During an "LOP-Loss of Prime" condition.
Closed: Volute-Thermostat digital input is active.
Closed: During a "High Feedback" condition as defined by P1-11 and P1-14 OR
High Feedback
Closed: During a "High FB/Water" fault OR
Closed: During a "High Feedback" alarm
Closed: During a "Low Feedback" condition as defined by P1-08 and P1-14 OR
Low Feedback
Closed: During a "Low FB/Water" fault OR
Closed: During a "Low Feedback" alarm
Closed: The drive is not running due to the Sleep function (does not include Sleep
Sleep Active
Boost).
Closed: Feedback has risen above the start level (or fallen below for Inverse PID)
Start Delay
and the start timer is timing.
Pre-Chg Active
Closed: Drive is in Pre-Charge mode.
Anti-Jam Active
Closed: The anti-jam function is active (configured by P7-oo).
Closed: The Thrust Bearing feature is active (output frequency is between 0 and
Thrust Mode
the value of P4-12).
Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to
Utility Delay
expire.
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
LCD Display
Term A1 Level
0: 0 to 10 V
0: 0-10V,
1: -10 to 10 V
(LowLim=0)
1: 0-10V, (BipolRef)
Sets the function of terminal A1.
Term A1 FuncSel
Sets the level of the input value selected in H3-02 when 10 V is
input at terminal A1.
Terminal A1 Gain
B.8 H Parameters: Multi-Function Terminals
Description
Description
Page
181
181
181
181
181
181
181
181
181
181
181
182
182
182
182
182
182
182
182
182
Values
Page
Default: 0
182
Range: 0, 1
Default: 0
183
Range: 0 to 41
B
Default: 100.0%
183
Min.: -999.9
Max.: 999.9
341