YASKAWA iQpump Micro CIMR-PW Series User Manual page 244

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

5.11 P: Pump
P9-32: Lag Follower Deceleration Time
n
Sets the deceleration time when the P9-33 timer is running and the drive is running as Lag Drive Speed Follower (P9-05 = 3).
No.
P9-32
P9-33: Lag Follower Deceleration Time Active Time
n
Sets the window during which the P9-32 deceleration time is effective. The drive will use the standard deceleration rates when
the P9-32 time expires.
A setting of 0.0 will disable the Lag Follower deceleration time switching.
No.
P9-33
P9-34: Low Feedback Quick De-Stage
n
Sets the low feedback level that will trigger a quick de-stage. The quick de-stage ignores parameters P9-12 to P9-15 and uses
an internal 2-second delay.
A setting of 0.0 disables the Low Feedback De-Stage feature.
No.
P9-34
P9-99: Network Compatibility Selection
n
Selects the communication compatibility for the iQpump MEMOBUS network.
No.
P9-99
Setting 0: A-Ver: 30034
Setting 1: B-Ver: 30035/36
Setting 2: iQ SmartNetwork
244
Name
Lag Follower Deceleration Time
Name
Lag Follower Deceleration Time Active Time
Name
Low Feedback Quick De-Stage
Name
Network Compatibility Selection
Setting Range
0.0 to 1000.0 s
Setting Range
0.0 to 360.0 s
Setting Range
0.0 to 6000.0
Setting Range
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
60.0 s
Default
0.0 s
Default
0.0 PSI
Default
0 to 2
0