YASKAWA iQpump Micro CIMR-PW Series User Manual page 92

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

4.8 iQpump Presets and Functions
H2-oo
Function
Setting
89
Output I Limit
The drive displays a message on the keypad when the drive is in output current limit.
Digital Operator Display
Current Limit Foldback
(CUr)
Speed Follower Deceleration Time Switchover
n
The iQpump Speed Follower will attempt to match the speed of the Lead Drive after the Lag Drive Fixed Speed Delay.
Consider a scenario wherein the system needs help from an idle drive to maintain system pressure. When the idle drive is
called to run, the difference between the setpoint and the feedback may be too small to make the drive accelerate faster. In
such cases, the system is configured with these settings:
• Set for Lag Drive Speed Follower
• Add Pump method is Frequency Reference
• Frequency Reference setting close to the maximum frequency
The system will drop the speed after the Lag Drive Fixed Speed Delay expires in order to follow the output frequency of the
previously idle drive. This transition may cause unwanted pressure drops. A longer deceleration time will be activated on the
lag drives when the system switches the drive that is being followed. The longer deceleration time will be effective for a
programmable setting, after which the regular deceleration time is used.
Functional Operation
If P9-05 = 3 (Follow Lead Spd), the lag drive will use the network information and the lead drive output speed as its frequency
reference. The lag drive final speed reference is affected by (Lag Follower Gain, P9-30) and then by (Lag Follower Bias,
P9-31).
Lag Drive Speed = ( Lead Drive Speed x Lag Follower Gain ) + Lag Follower Bias
When P9-33 > 0.0 sec, an alternate deceleration time (Lag Follower Decel, P9-32) is used when the drive switches from the
latched speed (Lag Fixed Delay, P9-07) to the new Lead drive output frequency. The deceleration time is active for the duration
set in P9-33, Lag Follower Deceleration Time Active Time, and will switch back to the regular deceleration rate when it
expires.
Note:
Parameter functionality stated below only applies when P1-01 = 3 (MEMOBUS Network)
Related Parameters
No.
Name
P9-05
Lag Drive Mode
P9-07
Lag Fixed Speed Delay
P9-30
Lag Drive Speed Follower Gain
P9-31
Lag Drive Speed Follower Bias
Lag Follower Deceleration
P9-32
Time
Lag Follower Deceleration
P9-33
Time Active Time
92
H2 Multi-Function Digital Output Settings
Closed: Drive output speed is being limited due to the output current limit or the single phase foldback
regulator.
Displayed when drive output speed is being limited due to the output current limit. Reduce the load or replace with
higher capacity drive.
Determines the functionality of the lag drives.
0: Fixed speed. The drive runs at the P9-06 setting after the time set in P9-07
expires.
2: Turn off. The drive stops running when it switches to a lag drive after the time
set in P9-07 expires.
3: Follow Lead Speed. The drive will follow the speed of the current lead drive,
applying P9-30 gain and P9-31 bias.
Specifies how long speed is latched before performing the function specified in
P9-05 when the drive changes from a lead to a lag.
Sets the gain to be applied to the speed of the current lead drive when P9-05 is set
to 3. The bias to be applied is set in P9-31.
Sets the bias to be applied to the speed of the current lead drive when P9-05 is set
to 3. The gain to be applied is set in P9-30.
Sets the deceleration time when the P9-33 timer is running and the drive is running
as Lag Drive Speed Follower (P9-05 is set to 3).
Sets the time during which the deceleration time set in P9-32 is effective. The drive
will use the standard deceleration rate when it expires.
Setting this parameter to 0.0 disables the function.
Description
Message
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Values
Default: 0
Range: 0, 2, 3
Default: 5 s
Min.: 0
Max.: 1000
Default: 100.0%
Min.: 0.0
Max.: 300.0
Default: 0.00 Hz
Min.: -60.0
Max.: 60.0
Default: 60.0 s
Min.: 0.0
Max.: 1000.0
Default: 0.0 s
Min.: 0.0
Max.: 360.0