YASKAWA iQpump Micro CIMR-PW Series User Manual page 266

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

6.3 Fault Detection
LED Display
LCD Display
The output current has fallen below the motor
underload curve defined in L6-14 for longer
than the time set to L6-03
LED Display
LCD Display
vu1
Cause
Input power phase loss
One of the drive input power wiring terminals
is loose
There is a problem with the voltage from the
drive input power
The power has been interrupted
The main circuit capacitors are worn
The relay or contactor on the soft-charge
bypass circuit is damaged
LED Display
LCD Display
vu2
Cause
L2-02 changed from its default value in drive
that is 7.5 kW or smaller without installing a
Momentary Power Loss Ride-Thru.
Control power supply wiring is damaged
Internal circuitry is damaged
LED Display
LCD Display
vu3
Cause
The relay or contactor on the soft-charge
bypass circuit is damaged
LED Display
LCD Display
ult5
Cause
266
Adjust the value set to L6-14 so that output current remains above the motor underload curve during normal
operation.
DC Bus Undervoltage
One of the following conditions occurred while the drive was running:
• Voltage in the DC bus fell below the undervoltage detection level (L2-05).
• For 200 V class: approximately 190 V (160 V for single phase drives)
Uv1
• For 400 V class: approximately 380 V (350 V when E1-01 is less than 400) The fault is output only if
L2-01 = 0 or L2-01 = 1 and the DC bus voltage is under L2-05 for longer than L2-02.
The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set to
L2-05 for longer than the time set to L2-02.
• The main circuit drive input power is wired incorrectly.
• Correct the wiring.
• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.
Tightening Torques on page 50
• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main circuit
magnetic contactor.
Correct the drive input power.
• Check the maintenance time for the capacitors (U4-05).
• Replace the drive if U4-05 exceeds 90%.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace the drive.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace the drive if U4-06 exceeds 90%.
Control Power Supply Voltage Fault
Uv2
Voltage is too low for the control drive input power.
Correct the setting to L2-02 or install an optional Momentary Power Loss Ride-Thru unit.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the control board, the entire drive, or the control power supply. For
instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the drive.
Undervoltage 3 (Soft-Charge Bypass Circuit Fault)
Uv3
The soft-charge bypass circuit failed.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace the drive.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace the drive if U4-06 exceeds 90%.
Volute-Thermostat Fault
VLTS
Fault Name
Fault Name
Possible Solution
for details.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Refer to Wire Gauges and

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents