Contactor Wiring Examples - Allen-Bradley Kinetix 5700 User Manual

Hide thumbs Also See for Kinetix 5700:
Table of Contents

Advertisement

Appendix A
Interconnect Diagrams

Contactor Wiring Examples

358
We recommend that you wire an Allen-Bradley® (Bulletin 100) auxiliary
contactor to the 2198-RPxxx regenerative-bus supply digital input (IOD
connector) and configure AC Line Contactor OK to monitor three-phase
input power. Use the Normally Open (N.O.) auxiliary contact, if more than
one auxiliary contact is available.
Figure 180 - Contactor Wiring for DC-bus Power Supply
2198-Pxxx
DC-bus Power Supply
Contactor Enable
CONT EN+
(CED) Connector
CONT EN–
L1
AC Input Power
L2
(IPD) Connector
L3
Figure 181 - Contactor Wiring for Regenerative Bus Supply
2198-RPxxx
Regenerative Bus Supply
CONT EN+
Contactor Enable
(CED) Connector
CONT EN–
L1
AC Input Power
L2
(IPD) Connector
L3
Digital Input
INx
(IOD) Connector
COM
(1) Configure digital input #2 as AC Line Contactor OK (default setting). For regenerative bus supply configurable functions, see the
Regenerative Bus Supply Configurable Functions
Refer to IEC Contactor Specifications Technical Data, publication
100-TD013, for additional contactor related information.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
24V DC
CONT EN+
CONT EN–
2198-DBRxx-F
AC Line Filter
24V DC
CONT EN+
CONT EN–
2198-DBRxx-F
AC Line
Filter
AC Line Filter
AUX N.O.
AUX N.C.
24V DC
table on
page
104.
Allen-Bradley
Bulletin 100 Contactor
L1
L1
L2
L2
L3
L3
Allen-Bradley
Bulletin 100 Contactor
L1
L1
L2
L2
L3
L3
AUX N.O.
AUX N.C.