Kinetix 5700 Accessory Modules
Module Status Indicator
MOD
DC BUS
DC-bus Status Indicator
MODULE
Module Status
STATUS
(MS) Connector

Kinetix 5700 Accessory Module Status Indicators

The Kinetix 5700 accessory modules include the 2198-CAPMOD-2240
capacitor module and 2198-DCBUSCOND-RP312 DC-bus conditioner
module.
Capacitor Module
Status indicators and the module status (MS) connector are on the front of the
module. The module status connector is an output suitable for wiring to a
DC-bus power supply, regenerative bus supply, or inverter digital input
assigned as Bus Capacitor OK, or the Logix 5000 controller.
Table 127 - Capacitor Module Status Indicators and Relay Output
Status
Indicators Status
Steady off
Steady green
Module
status
Steady red
Steady off
DC-bus
status
Steady green
(1) Wiring the module status relay output is optional.
DC-bus Conditioner Module
Status indicators and the module status (MS) connector are on the front of the
module. The module status connector is an output suitable for wiring to a
DC-bus power supply, regenerative bus supply, or inverter digital input
assigned as Bus Conditioner OK, or the Logix 5000 controller.
Table 128 - DC-bus Conditioner Module Status Indicators and Relay Output
Status
Status
Indicators
Steady off
Module
Steady green
status
(1)
Steady red
Steady off
DC-bus
status
Steady green
(1) Remove DC-bus power and cycle control power. If the fault persists, the internal fuse is blown and the module needs to be
replaced. If the fault clears, then there was a thermal fault caused by a system issue. If the fault persists and the rest of the
system is functioning properly, add more DC-bus conditioners to the system to reduce thermal stress on the module.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Troubleshoot the Kinetix 5700 Drive System
(1)
Relay
Description
Output
Open
24V DC is not present.
24V DC is present and
Closed
internal fuse is closed.
24V DC is present and
Open
internal fuse is open.
24V DC is not present or
Open
DC-bus measures < 50V DC. –
24V DC is present and
Closed
DC-bus measures > 50V DC.
Relay
Description
Output
Open
24V DC is not present
Closed
24V DC is present and internal fuse is closed
• 24V DC is present and internal fuse is open
Open
• Over temperature event occurred
24V DC is not present or DC-bus measures < 50V DC
24V DC is present and DC-bus measures > 50V DC
Chapter 7
Resolution
• Cycle control and bus power
• Verify that AC input meets
specifications
• Replace the module if fault persists
279