24V Input Power Connection System - Allen-Bradley Kinetix 5700 User Manual

Hide thumbs Also See for Kinetix 5700:
Table of Contents

Advertisement

Zero-stack Tab
and Cutout Engaged
Kinetix 5700 Drive System
DC-bus power supply is mounted
leftmost followed by drive with
largest amp rating.
DC-bus Power Supply
Figure 49 - DC-bus Connector Example
DC-bus Link, 85 mm
DC-bus Link, 100 mm
(seated)
(1) DC-bus links latch on both sides when inserted into the DC-bus connectors. To remove the DC-bus link, depress both sets of
upper pivots to unlatch the lower pivots and hold the DC-bus link firmly while pulling upward.

24V Input Power Connection System

The optional 24V input power connection system always feeds 24V DC from
left to right and is comprised of three components:
• The 24V input wiring connector that plugs into the DC-bus power
supply or first module supplied by the 24V external power receives 24V
DC input wiring.
• 24V DC T-connectors that plug into the drive modules downstream
from the power supply or first module supplied by the 24V external
power where the 24V control power is shared.
• Bus bars that connect between drive modules to extend the 24V control
power from one drive module to another.
Multiple 24V shared-bus input wiring connectors can be used in a high axis-
count system. If the 40 A shared-bus current rating is exceeded, you can add
another connector at any point in the cluster. 2198-S263-ERSx and
2198-S312-ERSx drives and 2198-RP263 and 2198-RP312 bus supplies use
the 2198T-W25K-P-IN input wiring connector. All other modules use the
2198-TCON-24VDCIN36 input wiring connector. Both wiring connectors
2
accept up to 10 mm
each module accept up to 10 mm
shared-bus input wiring connectors can provide the means to use larger gauge
conductors for reduced voltage drop on long wire runs.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Mount the Kinetix 5700 Drive System
End Caps (2)
DC-bus Link, 55 mm
(6 AWG) wire. The CP connectors that are included with
2
(12 AWG) or 6 mm
Chapter 3
Align the DC-bus link
lower pivots with the
latches and push downward
until they latch.
Upper Pivot
Lower Pivot
Latch
(1)
DC Link Latched
Dual Axis Inverter, 55 mm
Single Axis Inverter, 85 mm
Single Axis Inverter, 100 mm
2
(10 AWG), so the
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents