Chapter 2
Plan the Kinetix 5700 Drive System Installation
DC-bus Power Supply
Cat. No.
2198-P031
2198-P070
2198-P141
2198-P208
2198-P208 (2 in parallel)
2198-P208 (3 in parallel)
(1) Auxiliary contact configuration 10 indicates there is 1 N.O. and 0 N.C. contacts. Other configurations are available.
(2) For contactors that are not Bulletin 100-E type, the integrated diode is required with the contactor coil. See Knowledgebase document
(3) These DC-bus power supplies require an additional intermediate relay used with the contactor.
Regenerative Bus Supply
Cat. No.
2198-RP088
2198-RP200
2198-RP263
2198-RP312
(1) Auxiliary contact configuration 10 indicates there is 1 N.O. and 0 N.C. contacts. 11 indicates there is 1 N.O. and 1 N.C. contact. Other configurations are available.
(2) These contactor catalog numbers include a 24V DC coil. For contactors that are not Bulletin 100-E type, see Knowledgebase document
50

Contactor Selection

The AC three-phase contactor control string must be wired in series with the
contactor-enable relay at the CED connector. The contactor-enable relay
(applies to 2198-Pxxx DC-bus power supply and 2198-RPxxx regenerative bus
supply) is rated at 24V DC (28V, max) and 1.0 A, max.
IMPORTANT Applying more than 28V DC control voltage or more than 1.0 A control
current to the contactor can cause permanent damage to the DC-bus power
supply or regenerative bus supply.
ATTENTION: Wiring the contactor-enable relay is required. To avoid personal
injury or damage to the system, wire the contactor-enable relay into your
control string so that:
• three-phase power is removed and the power supply is protected under
various fault conditions.
• three-phase power is never applied to the Kinetix 5700 drive system before
control power is applied.
Contactor with auxiliary contacts is strongly recommended when used with
2198-RPxxx regenerative bus supply. Wire auxiliary contact to digital input #2
(default setting) to monitor the three-phase input power. See
Wiring Examples
on
Table 13 - DC-bus Power Supply Contactor Specifications
(1) (2)
Contactor
Cat. No.
100-C16EJ10
100-C37EJ10
100-C72DJ10
100-C97DJ10
100-E190KJ11
100-E305KJ11
Table 14 - Regenerative Bus Supply Contactor Specifications
(1) (2)
Contactor
Cat. No.
100-C43EJ10
100-E116KJ11
100-E205KJ11
100-E265KJ11
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
page 358
for wiring examples.
Intermediate Relay
Cat. No.
N/A
700-HB32Z24 (relay)
700-HN153 (socket)
19362
for more information.
Intermediate Relay
Cat. No.
N/A
19362
for more information.