Converter OK Relay

The converter OK circuitry includes a relay-driven contact within the
2198-RPxxx regenerative bus supply. The relay provides a 24V signal to non-
Kinetix 5700 inverters indicating that they can draw power from the
regenerative power supply and that the power supply is not faulted.
TIP This signal is intended for use with Kinetix 6000, Kinetix 6200, Kinetix 6500
Kinetix 7000, or PowerFlex drives when migrating from the 8720MC-RPS to
the 2198-RPxxx regenerative bus supply.
Refer to
Power Wiring Examples
Figure 67 - Converter OK Relay Circuit
Internally
Controlled
Regenerative
Bus Supply
Current limited output with auto-resettable fuse.
Table 49 - Converter OK Relay Output Specifications
Attribute
Value
On-state current
Current flow when the relay is closed.
Off-state voltage
Voltage across the contacts when the relay is open
or closed.
On-state voltage

Motor Brake Circuit

The brake option is a spring-set holding brake that releases when voltage is
applied to the brake coil in the motor. The customer-supplied 24V power
supply drives the brake output through a solid-state relay. The dual-axis
inverters have separate brake circuits for each axis. The solid-state brake driver
circuit provides the following:
• Brake current-overload protection
• Brake over-voltage protection
For a detailed information on vertical loads and how the servo motor holding-
brake option can be used to help keep a load from falling, see the Vertical Load
and Holding Brake Management Application Technique, publication
MOTION-AT003.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Connector Data and Feature Descriptions
on
page 343
for wiring examples.
24V PWR
Relay
OK+
Resettable Fuse
OK–
24V COM
Chapter 4
Min
Max
0.8 A
0V DC
24V DC
111