Chapter 7
Troubleshoot the Kinetix 5700 Drive System
Kinetix 5700 Modules
Module Status
Network Status
Ethernet RJ45 Connectors
Link Speed
Status Indicators
Link/Activity
Status Indicators
278

Kinetix 5700 Status Indicators

These status indicators apply to the Kinetix 5700 DC-bus power supply, the
regenerative bus supply, the inverters, and the iTRAK® power supply. The
module status and network status indicators are just above the LCD status
display.
IMPORTANT Status indicators are not reliable for safety functions. Use them only for
general diagnostics during commissioning or troubleshooting. Do not
attempt to use status indicators to determine operational status.
Table 123 - Module Status Indicator
Condition
Status
Steady Off
No power applied to the drive.
Steady Green
Drive is operational. No faults or failures.
Flashing Green
Standby (drive not configured) and Precharge (drive is configured).
Major recoverable fault. The drive detected a recoverable fault, for example, an incorrect
Flashing Red
or inconsistent configuration.
Steady Red
Major fault. The drive detected a non-recoverable fault.
Self-test. The drive performs self-test during powerup. Once self-test is complete,
Flashing Green/Red condition continues if drive is waiting for:
Flashing Green/Red
• Safety configuration when in Integrated STO mode
• Safety inputs when in Hardwired STO mode
Table 124 - Network Status Indicator
Condition
Status
Steady Off
No power applied to the drive or IP address is not configured.
Flashing Green
No Motion or Safety connection is established, but drive has obtained an IP address.
Motion or Safety connection is established and no timeout has occurred. Normal
Steady Green
operation.
Connection timeout. One or more of the connections, for which this drive is the target,
Flashing Red
has timed out.
Steady Red
Duplicate IP address. IP address specified is already in use.
Self-test. The drive performs self-test during powerup. Once self-test is complete,
Flashing Green/Red
Flashing Green/Red condition continues if drive is processing a safety device ID proposal.
Table 125 - Ethernet Link Speed Status Indicator
Condition
Status
Steady Off
10 Mbit
Steady On
100 Mbit
Table 126 - Ethernet Link/Activity Status Indicator
Condition
Status
Steady Off
No link
Steady On
Link established
Blinking
Network activity
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019