Appendix E
Motor Control Feature Support
418
Once rated flux is reached in the motor, normal operation can begin and the
desired acceleration profile achieved.
Figure 223 - Rated Flux Reached
Greater of IR Voltage or
Voltage Boost - V/Hz
Flux Up
Voltage
Flux Up

Flux Up Attributes

ID
Access
Attribute
558
Set
Flux Up Control
559
Set
Flux Up Time
(1) This is the time designated for the Manual Delay setting. This attribute is not supported by the Automatic delay method. The
flux-up feature is disabled if FluxUpControl is set to Manual Delay and FluxUpTime is set to 0.
FluxUpControl Attribute
When the motion axis is enabled, DC current is applied to an induction motor
to build stator flux before transitioning to the Running state. This attribute
controls how an induction motor is to be fluxed in the Starting state prior to
transitioning to the Running state.
Table 188 - FluxUp Control Delay Methods
Delay Method
Description
No delay
The axis transitions immediately to the Running state while the motor flux is building.
The axis remains in the Starting state while the motor stator flux is building according to the
Manual delay
Flux Up Time attribute.
The drive determines the amount of delay time to fully flux the motor based on the motor
Automatic delay
configuration attribute data or measurements.
FluxUpTime Attribute
When FluxUpControl is configured for Manual Delay, this attribute sets the
length of delay time to fully flux the motor before transitioning to the Running
state.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
IR Voltage - SVC
Stator Voltage
Rotor Speed
Motor Flux
Stator Frequency
Normal Operation
Time
Conditional Implementation
Ind Motor only
0 = No Delay
1 = Manual Delay
2 = Automatic Delay
Ind Motor only
Units: Seconds
(1)
Default: 0.0000
Min/Max: 0.0000 / 1000.00