Active Shunt Wiring Examples - Allen-Bradley Kinetix 5700 User Manual

Hide thumbs Also See for Kinetix 5700:
Table of Contents

Advertisement

Appendix A
Interconnect Diagrams
Active Shunt Wiring
Examples
DC-Bus Power Supply
Regenerative Bus Supply
360
Active shunts are available from the Rockwell Automation Encompass™ partner
Powerohm Resistors, Inc. (http://www.powerohm.com).
IMPORTANT Powerohm Bulletin PKBxxx active shunt modules use built-in internal brake
For compatible Powerohm active shunts paired with 2198-Pxxx DC-bus
power supplies and 2198-RPxxx regenerative bus supplies, see
shunt Connections
Figure 184 - 2198-RPxxx Supply with External Active Shunt (built-in brake resistor)
2198-RPxxx
Regenerative Bus Supply
Shunt (RC)
Connector
Digital Input
(IOD) Connector
(1) The active shunt (RC) connector is rated for wire size up to 6 mm
connect to the shunt, the drive connection must be made to the external DC-bus connections on an accessory module.
(2) Configure any available digital input as Shunt Thermal Switch OK. See the
(3) Powerohm PKB050 and PKB050-800 shunts require 120V AC between pins 9 and 10 to supply power to the cooling fans.
Figure 185 - 2198 Power Supply with External Active Shunt (built-in brake resistor)
2198-Pxxx
2198-xxxx-ERSx
Inverter
Capacitor Module
or
2198-RPxxx
Digital Input
INx
(1)
(IOD) Connector
COM
(1) Configure any available digital input as Shunt Thermal Switch OK. See the
(2) Powerohm PKB050 and PKB050-800 shunts require 120V AC between pins 9 and 10 to supply power to the cooling fans.
See Knowledgebase document
these Powerohm Bulletin PKBxxx active shunts.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
resistors. Bulletin PWBxxx active shunt modules require appropriately sized
external brake resistors.
on
page
183.
ATTENTION: To avoid damage to the Kinetix 5700 drive system, wire the
active shunt thermal switch to a digital input on the power supply and
configure the Shunt Thermal Switch OK function in the Logix Designer
application.
DC+
(1)
DC–
4.6 m (15 ft) Maximum Cable Length
(2)
INx
COM
2198-
CAPMOD-2240
4.6 m (15 ft) Maximum Cable Length
DC+
External DC-bus
DC–
1082776
External Active-
Powerohm
Bulletin PKB-xxx-xxx
Active Shunt Module
DC+
Resistor
DC–
3
Fault Contact
4
24V DC
2
(10 AWG). When conductors larger than 6 mm
Digital Inputs Connector Pinouts
Powerohm
Bulletin PKBxxx-xxx
Active Shunt Module
DC+
Resistor
DC–
3
Fault Contact
4
24V DC
Digital Inputs Connector Pinouts
for more information on wiring to
(3)
9
120V AC
10
2
(10 AWG)
on
page
103.
(2)
9
120V AC
10
on
page
103.