Mount Accessory Modules

Mount the 2198-CAPMOD-2240 capacitor module on the far right or far left
of any system cluster, depending on the input power configuration. A capacitor
module is required in the following situations:
• Required in each cluster of a multi-cluster system
• More than one capacitor module can be used in a cluster, if needed
IMPORTANT Each additional capacitor module adds to the total system capacitance and
increased energy storage.
The 2198-CAPMOD-DCBUS-IO extension module is always mounted next
to a capacitor module or DC-bus conditioner module and always positioned
on the outside of the system cluster (either first or last). The extension module
can be paired with another accessory module and flexible bus-bars if external
DC-bus current is ≥104 A up to a maximum of 208 A.
IMPORTANT When the extension module is mounted next to another accessory module,
they must be connected by flexible bus bars.
Figure 47 - Flexible Bus Bar Example
Flexible Bus-bars
DC-bus Link
Connections
1
9
2198-xxxx-ERSx
Inverters
8
16
IMPORTANT In a multi-cluster system with a power supply rated ≥104 A, two accessory
modules connected by flexible bus bars must be used to create a 208 A
extended cluster system. See the
table on
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Mount the Kinetix 5700 Drive System
External DC-bus
Wire Lug Connections
DC-bus Links
SB+/NC
S1A
SCA
S2A
SB-
NC
NC
NC
Accessory Module Connector Specifications
page 181
for DC-bus wiring requirements.
Chapter 3
2198-CAPMOD-DCBUS-IO
Extension Module
2198-DCBUSCOND-RP312
DC-bus Conditioner Module
83