Regenerative Bus Supply
Input Voltage
Cat. No.
(three-phase) nom
2198-RP088
2198-RP200
324...506V AC rms
2198-RP263
2198-RP312
(1) Applies when DC-bus voltage regulation is enabled. If DC-bus voltage regulation is not enabled, then the input voltage range is 324....528V AC. For more information on these two modes of
operation, see
DC-bus Voltage Regulation
Table 12 - Regenerative Bus Supply IEC (non-UL/CSA) Circuit-protection Specifications
(1)
DIN gG Fuses
Amps, max
50
125
200
250
on
page
42.
Refer to the Kinetix Servo Drives Technical Data, publication KNX-TD003,
for additional power specifications for your 2198-Pxxx DC-bus power supply
and 2198-RPxxx regenerative bus supply.

24V Control Power Evaluation

The Kinetix 5700 drive system requires 24V DC input for its control circuitry.
Due to the 24V shared-bus connection system and the 24V current
requirements of the Kinetix 5700 drives, a thorough evaluation of control
power is required prior to implementation. Consider the following when sizing
such a system:
• Verify that the 24V DC power supply is capable of supplying the 24V
current requirements of your Kinetix 5700 drive system. See
24V DC Control Power Current Demand
24V current requirements. For systems with a high 24V current demand,
consider the following:
– Install separate 24V power supplies for each cluster or change the
cluster configuration to more evenly divide the 24V current demand.
– Install separate 24V power supplies for each Bulletin 2198 power
supply and inverter.
• Verify that the wiring being used is capable of supplying the
Kinetix 5700 drive system with a voltage within the 24V input-voltage
range; 24V ±10% (21.6...26.4V DC). Consider the following:
– Mount the 24V power supply as close to the Kinetix 5700 drive
system as possible to minimize input voltage drop.
– Install larger gauge wire, up to 4 mm
AWG) for 24V control power when using the CP connectors
included with the module; or use the 24V shared-bus connection
system to lower the DC wire resistance with up to 10 mm
and result in a lower voltage drop.
IMPORTANT The 24V current demand, wire gauge, and wire length all impact the voltage
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Plan the Kinetix 5700 Drive System Installation
Miniature CB
Cat. No.
1489-M3C600
1492-SPM3C630 140MG-H8E-C60
drop across the wiring being used. For an example, see
Calculation Example
on
page
397.
Motor Protection CB
Molded Case CB
Cat. No.
Cat. No.
140G-G6C3-C60
140MG-J8E-D15
140G-J6F3-D15
140G-K6F3-D30
140G-K6F3-D40
Calculate
on
page 396
to determine the
2
2
(12 AWG) and 6 mm
(10
2
(6 AWG)
24V DC Voltage Drop