Wire The Contactor Enable Connector - Allen-Bradley Kinetix 5700 User Manual

Hide thumbs Also See for Kinetix 5700:
Table of Contents

Advertisement

Chapter 5
Connect the Kinetix 5700 Drive System
EN–
EN+
Regenerative Bus Supply
Cat. No.
2198-RP088
2198-RP200
2198-RP263
2198-RP312
148

Wire the Contactor Enable Connector

The contactor enable (2-pin CED) connector applies to the DC-bus power
supply. The regenerative bus supply has a 4-pin CED connector and includes
wiring to the Converter OK relay.
Figure 96 - CED Connector Wiring - Connector Plug
2198-Pxxx
MOD–
NET–
DC-bus Power Supply
(front view)
2
1
1
2-pin Contactor Enable
4
I/O
(CED) Connector Plug
Table 73 - CED Connector Plug Specifications
DC-bus Power Supply
Pin
Cat. No.
2198-P031
2198-P070
EN–
2198-P141
EN+
2198-P208
OK+
OK–
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
ATTENTION: Wiring the contactor enable relay is required. To avoid personal
injury or damage to the Kinetix 5700 drive system, wire the contactor enable
relay into your control string so that:
• three-phase power is removed and the DC-bus power supply or regenerative
bus supply is protected under various fault conditions.
• three-phase power is never applied to the Kinetix 5700 drive system before
control power is applied.
2198-RPxxx
MOD
NET
5700
Regenerative Bus Supply
(front view)
2
1
I/O
4-pin Contactor Enable
1
6
OK+
OK–
EN–
(CED) Connector Plug
EN+
5
10
Recommended
Wire Size
Signal
2
mm
CONT EN–
CONT EN+
0.14...2.5
(26...12)
CONV OK+
CONV OK–
Strip Length
Torque Value
mm (in.)
N•m (lb•in)
(AWG)
0.4...0.5
7.0 (0.28)
(3.5...4.4)
OK+
OK–
EN–
EN+

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents