Chapter 9
Kinetix 5700 Safe Torque-off Function
2198-Sxxx-ERSx
Single-axis Inverter
Safety (STO) Connector Plug
320

Safe Torque-off Wiring Requirements

The safe torque-off (STO) connector uses spring tension to secure the wire.
Depress the numbered tab along side each pin to insert or release each wire.
Two rows of pins are provided for drive-to-drive connections. Wire must be
copper with 75 °C (167 °F) minimum rating.
IMPORTANT The National Electrical Code and local electrical codes take precedence over
IMPORTANT Stranded wires must terminate with ferrules to prevent short circuits, per
Figure 148 - Safe Torque-off (STO) Terminal Plug
Safety (STO) Connector Plug
Table 160 - Safe Torque-off (STO) Connector Plug Wiring
Safe Torque-off
(STO) Connector Signal
STO Pin
2198-Dxxx-ERSx
1
SB+
2
10
S1A
3
11
SCA
4
12
S2A
5
13
SB-
6
14
S1B
7
15
SCB
8
16
S2B
9
NC
(1) This connector uses spring tension to hold wires in place.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
the values and methods provided.
table D7 of ISO 13849.
2198-Dxxx-ERSx
Dual-axis Inverter
Recommended Wire Size
2
mm
(AWG)
2198-Sxxx-ERSx
SB+
S1
SC
S2
0.14...1.5
SB-
(26...16)
NC
NC
NC
NC
Kinetix 5700 Inverter, Top View
(2198-D057-ERS4 dual-axis
inverter is shown)
Strip Length
Torque Value
mm (in.)
N•m (lb•in)
(1)
10 (0.39)
N/A