Figure 144 - System Operation when Safety Enable Inputs Mismatch Momentarily
Safety Input S1
Safety Input S2
GuardFault
SafeTorqueOffInhibit
GuardOKStatus
GuardGateDriveOutputStatus
GuardStopInputStatus
GuardStopRequestStatus
GuardStopInputFault
ATTENTION: The safe torque-off fault is detected upon demand of the safe
torque-off function. After troubleshooting the STO function or performing
maintenance that might affect the STO function, the STO function must be
executed to verify correct operation.
IMPORTANT The GuardStopInputFault can be reset only if both inputs are in the OFF-
state for more than 1 second. After the fault reset requirement is satisfied,
an MAFR command in the Logix Designer application must be issued to
reset the GuardStopInputFault.

Safe Torque-off Connector Data

Two rows of eight pins are provided for making drive-to-drive connections.
The dual-axis inverters have pins designated for axis A and axis B. The single-
axis inverters do not use STO-6, -7, -8 and STO-14, -15, -16.
Figure 145 - Pin Orientation for 16-pin Safe Torque-off (STO) Connector
2198-Dxxx-ERSx
Dual-axis Inverter
Safety (STO) Connector Plug
9
1
10
2
3
11
4
12
5
13
14
6
15
7
16
8
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Kinetix 5700 Safe Torque-off Function
1 Second
No Fault
OK
No Fault
Single-axis Inverter
Safety (STO) Connector Plug
SB+/NC
S1A
SCA
S2A
SB-
S1B
SCB
S2B
Chapter 9
Faulted
Start Inhibited
Not OK
Torque Disabled
Stop Requested
Faulted
2198-Sxxx-ERSx
SB+/NC
1
9
S1A
2
10
SCA
11
3
S2A
12
4
SB-
13
5
N/C
6
14
N/C
7
15
N/C
8
16
317