Chapter 5
Connect the Kinetix 5700 Drive System
Active Shunt (RC) Connector Plug
184
Connections at the Active Shunt (RC) Connector
You can make active shunt connections in drive systems that include the
regenerative bus supply and Powerohm PKBxxx-800 active shunts at the Active
Shunt (RC) connector.
Figure 124 - RC Connector Wiring
Table 100 - Active Shunt (RC) Connector Specifications
Regenerative
Bus Supply
Pin
Cat. No.
RC-1
2198-RPxxx
RC-2
(1) This connector applies to only Powerohm PKBxxx-xxx active shunts rated at 7 kW or less.
IMPORTANT Due to the 10 A connector current rating, connections to the RC connector
are limited to only Powerohm PKBxxx-xxx active shunts rated at 7 kW or less.
All other PKBxxx-xxx and PWBxxx-xxx active shunt connections must be
made to the 2198-CAPMOD-2240 capacitor module.
Connections at the External DC-bus Studs
You can make active shunt connections in drive systems that include the
regenerative bus supply and Powerohm PKBxxx-800 or PWBxxx-800 active
shunts at the external DC-bus studs on accessory modules.
Refer to
Wire the External DC-bus

Wire the External DC-bus Connections

Accessory modules are equipped with spacers that slide onto the M8 studs.
When the system configuration includes external DC-bus and active shunt
connections, external DC-bus connections are made below the spacer and
active shunt connections are made above the spacer.
Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Recommended
(1)
Continuous
Wire Size
Signal
Current, max
2
mm
(AWG)
DC–
2.5...6
10 A
DC+
(14...10)
Connections.
2198-RPxxx
Regenerative Bus Supply
Top View
Strip Length
Torque Value
mm (in.)
N•m (lb•in)
0.5...0.6
12.0 (0.47)
(4.4...5.3)