Connecting To Sdc20/21, Sdc30/31; Connecting To Cmc10L - Mitsubishi Electric GOT2000 Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000:
Table of Contents

Advertisement

3.5.4
Connecting to SDC20/21,
SDC30/31
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps
Transmission speed
Data bit
8bits
Parity bit
Disable
Stop bit
2bits
*2*3
0 to 127
Station address
*1
The transmission speed setting must be consistent with that
of the GOT side.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.5

Connecting to CMC10L

Communication settings
Make the communication settings by operating the DIP
switch of the Interface converter
Item
*1
Transmission speed
*2
Frame length
*1
The transmission speed setting must be consistent with that
of the GOT side.
*2
The sum of data length, parity bit and stop bit
Settings by switch
Front view of CMC10L body
3 - 52
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.5 Control Equipment Side Setting
Set value
Set value
9600bps, 19200bps, 38400bps
9 to 15bits
DIP switch
Mode selector
switch
Rear view of CMC10L body
(1) Setting DIP switches
(a) Transmission speed settings
Switch No.
Transmission
speed (bps)
1
2
9600
ON
OFF
19200
OFF
ON
38400
ON
ON
(b) Frame length settings
Switch No.
Frame length
4
5
8bits
OFF
OFF
9bits
ON
OFF
10bits
OFF
ON
11bits
ON
ON
12bits
OFF
OFF
13bits
ON
OFF
14bits
OFF
ON
15bits
ON
ON
(c) Connecting terminating resistors
Switch No.
Terminating
resistor
8
Enable
ON
Disable
OFF
(2) Mode selector switch settings
Set the switch to "TERMINAL".
3
Set these
switches
ON
ON
ON
6
OFF
OFF
Set these
OFF
switches
OFF
ON
ON
ON
ON
Set these
switches