3.5.4
Connecting to SDC20/21, SDC30/31
■1. Communication settings
Make the communication settings by operating the key of the temperature controller.
*1
Transmission speed
Data bit
Parity bit
Stop bit
*2*3
Station address
*1
*2
*3
3.5.5
Connecting to CMC10L
■1. Communication settings
Make the communication settings by operating the DIP switch of the Interface converter
*1
Transmission speed
*2
Frame length
*1
*2
■2. Settings by switch
(1) Setting DIP switches
(a)
Transmission speed settings
3 - 62
3.5 Control Equipment Side Setting
Item
The transmission speed setting must be consistent with that of the GOT side.
Do not set to "0".
Select the station address without overlapping with that of other units.
Item
The transmission speed setting must be consistent with that of the GOT side.
The sum of data length, parity bit and stop bit
Front view of CMC10L body
Transmission speed (bps)
9600
19200
38400
9600bps
8bits
Disable
2bits
0 to 127
9600bps, 19200bps, 38400bps
Rear view of CMC10L body
Set these
switches
1
ON
OFF
ON
Set value
Set value
9 to 15bits
DIP switch
Mode selector
switch
Switch No.
2
OFF
ON
ON
3
ON
ON
ON