Advanced commissioning
8.18 Setpoint processing
8.18.3
Inhibit direction of rotation
Function description
In the factory setting of the converter, both motor directions of rotation are enabled.
Set the corresponding parameter to a value = 1 to permanently block directions of rotation.
Example
Table 8-50
Parameter
p1110[0] = 1
p1110[0] = 722.3
Parameter
Parameter
p1110[C]
p1111[C]
282
Application examples for inhibiting and enabling a direction of rotation
Description
Negative direction of rotation is permanently inhibited.
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Description
BI: Inhibit negative direction
BI: Inhibit positive direction
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Factory setting
0
0
SINAMICS G120C Converters