Enable Direction Of Rotation; Minimum Speed - Siemens SINAMICS G120 Original Instructions Manual

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

8.4.3

Enable direction of rotation

In the factory setting of the inverter, the negative direction of rotation of the motor is inhibited.
Procedure
Proceed as follows to permanently enable the negative direction of rotation:
Set parameter p1110 to a value = 0.
You have permanently enabled the negative direction of rotation.
Table 8- 16
Parameter
p1110 = 1
p1110 = 722.3
8.4.4

Minimum speed

The inverter prevents continuous motor operation
at speeds < minimum speed.
Speeds, where the absolute value is less than the
minimum speed, are only possible when
accelerating or braking.
Table 8- 17
Parameter
p1080
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Examples of settings to inhibit the direction of rotation
Remark
Inhibit negative direction
Negative direction is permanently inhibited.
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Setting the minimum speed
Description
Minimum speed
Setting functions
8.4 Setpoint calculation
245

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120dCu230p-2

Table of Contents