Inhibit Direction Of Rotation - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

6.4.3

Inhibit direction of rotation

In the factory setting of the inverter, both motor directions of rotation are enabled.
Set the corresponding parameter to a value = 1 to permanently block directions of rotation.
Table 6- 27
Parameter
p1110 = 1
p1110 = 722.3
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Examples of settings to inhibit the direction of rotation
Remark
Inhibit negative direction
Negative direction is permanently inhibited.
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Advanced commissioning
6.4 Setpoint calculation
217