Setting functions
8.4 Setpoint calculation
8.4.3
Inhibit direction of rotation
In the factory setting of the inverter, both motor directions of rotation are enabled.
Set the corresponding parameter to a value = 1 to permanently block directions of rotation.
Table 8- 9
Parameter
p1110 = 1
p1110 = 722.3
128
Examples of settings to inhibit the direction of rotation
Remark
Inhibit negative direction
Negative direction is permanently inhibited.
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA