Tm31 Analog Outputs - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Output terminals

8.2 TM31 analog outputs

8.2
TM31 analog outputs
Description
The TM31 terminal block module features two analog outputs for outputting setpoints via
current or voltage signals.
Delivery condition:
● AO0: Actual speed value: 0 – 10 V
● AO1: Actual motor current: 0 – 10 V
Preconditions
● The Power Module, CU320-2, and TM31 have been correctly installed.
● The "TM31 terminals" or "PROFIdrive+TM31" default setting was chosen during
commissioning:
STARTER:
AOP30:
Signal flow diagram
Figure 8-1
Signal flow diagram: analog output 0
Function diagram
FP 1840,
FP 9572
370
"TM31 terminals" or "PROFIdrive+TM31"
"2: TM31 terminals" or "4: PROFIdrive+TM31"
TM31 - analog outputs (AO 0 ... AO 1)
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A