4.3.4.2 Defining the parameter Counts Per Meter (DSQC 2000)

Introduction
The Counts Per Meter system parameter is used to calibrate the conveyor encoder.
The Counts Per Meter system parameter belongs to the type Conveyor Ici, in the
topic Process.
xx2100000042
Calculation for Counts Per Meter
The value for the Counts Per Meter system parameter is calculated as follows:
counts value/measured_meters
Value
counts value
measured_meters
Defining Counts Per Meter
Use the following procedure to define Counts Per Meter for the conveyor encoder.
Application manual - PickMaster® Twin - PowerPac
3HAC064218-001 Revision: B
4.3.4.2 Defining the parameter Counts Per Meter (DSQC 2000)
1 Put a mark on the conveyor belt, for example draw a line or attach a piece
of tape, and a mark on the side of the conveyor at the same location.
2 In the FlexPendant Program Editor, load and run the program ppacal.prg.
This sets the current position of the conveyor to zero. The value is shown
as CNV value in the Position part of the FlexPendant Jogging window.
3 Run the conveyor belt approximately 1 meter.
4 In the FlexPendant Jogging window, read the position of the conveyor. This
is position1.
5 Measure the physical distance between the two marks. This is the value
measured_meters.
© Copyright 2021 ABB. All rights reserved.
4 Working with PickMaster PowerPac
Description
The conveyor position after moving.
For DSQC 2000: Read from predefined I/O signal on the
FlexPendant or RobotStudio. For example, CNV1, the
signal name is c1counts.
The manually measured distance in meters that the
conveyor has been moved.
Continues on next page